Wire Gauge Converter

Convert AWG to cross-sectional area, diameter or circular mils. Enter a value, choose the units, then press Convert.

Written and reviewed by SM Arijul Islam · Last reviewed · Editorial standards · Report an error

About the Wire Gauge Converter

American Wire Gauge runs backwards: a smaller number is a thicker wire. AWG 10 is 2.59 mm in diameter and 5.26 mm² in area; AWG 20 is 0.812 mm and 0.518 mm². The scale is logarithmic, with each three-gauge step roughly halving the area.

The defining formula is d = 0.127 × 92^((36 − AWG)/39) mm, where 0.127 mm is AWG 36. Cross-sectional area is πd²/4. Circular mils are a US convention: one circular mil is the area of a circle one thousandth of an inch across, so CMA = d² in mils.

How the calculation works

  • Diameter (mm) = 0.127 × 92^((36 − AWG) ÷ 39).
  • Area (mm²) = π × diameter² ÷ 4.
  • 1 circular mil = 0.000506707 mm².
  • Each 3 AWG steps roughly doubles or halves the area.

Reference values

Common wire gauges
AWGDiameter (mm)Area (mm²)Typical use
83.2648.37High-current battery cable
102.5885.26Solar and heavy DC
122.0533.3120 A house circuits
141.6282.0815 A lighting circuits
181.0240.823Low-voltage wiring
220.6440.326Signal and control
240.5110.205Ethernet / data
300.2550.051Fine electronics

Worked example: AWG 12 and its neighbours

AWG 12 is 2.053 mm in diameter and 3.31 mm² in area. Three gauges finer, AWG 15, is 1.450 mm and 1.65 mm²—almost exactly half the area. Three gauges thicker, AWG 9, is 2.906 mm and 6.63 mm²—almost exactly double. That logarithmic step is why a small change in AWG number can matter more than it looks.

AWG 12 is often protected at 20 A in a residential branch circuit, but ampacity is not a property of the wire alone. Insulation temperature rating, bundling, conduit fill and ambient temperature all change the safe current. Check the local electrical code and the manufacturer's table before choosing a breaker.

AWG, SWG and metric wire

American Wire Gauge is not the only gauge in use. Standard Wire Gauge, still found in older British equipment, runs the opposite way for some sizes, and metric wire is sold by cross-sectional area in square millimetres. The same nominal number can therefore describe different conductors: 12 AWG is 3.31 mm², while a “12 gauge” in a metric catalogue may mean 4 mm².

When replacing cable, match the cross-sectional area and the insulation rating rather than the gauge number alone. A conductor that is slightly larger is safe for current but may not fit a terminal, and one that is slightly smaller may overheat. The printed markings on the cable sheath are the authority.

Frequently asked questions

No. Higher AWG numbers are thinner wires. AWG 12 is thicker than AWG 18.
The gauge is a logarithmic scale. Every 6-gauge step is about a factor of four in area, and every 3-gauge step about a factor of two.
No. Ampacity depends on insulation temperature rating, bundling, ambient temperature and installation method. Use a wire gauge chart or local code.
For the same insulation and installation conditions, yes. Ampacity also depends on temperature rating, bundling, conduit fill and ambient temperature, so follow the local electrical code.