AWG to mm² Converter

Pick an AWG size or a cross-section and press Convert. AWG numbers run backwards: a lower number is a thicker wire.

Written and reviewed by SM Arijul Islam · Last reviewed · Editorial standards · Report an error

About the AWG to mm² Converter

Converting AWG to mm2 is not a linear step. AWG is a logarithmic standard, so each step of three roughly halves the cross-sectional area. That is why 12 AWG (3.31 mm²) and 14 AWG (2.08 mm²) are a step apart and 10 AWG (5.26 mm²) is double the 12.

Metric cable is sold by cross-section, so an imperial drawing and a European cable schedule do not match exactly: 12 AWG is 3.31 mm², which is nearer to 2.5 mm² or 4 mm² than to a metric size of its own. For anything carrying current, use the ampacity table for the cable you actually have.

How the calculation works

  • Area (mm²) = 0.012668 × 92^((36 − AWG) ÷ 19.5)
  • Diameter (mm) = 0.127 × 92^((36 − AWG) ÷ 39)
  • 12 AWG = 3.31 mm² · 14 AWG = 2.08 mm² · 16 AWG = 1.31 mm²

Reference values

Wire gauge chart with cross-sectional area
AWGmm²Typical use
6 AWG13.30 mm²Service entrance
8 AWG8.37 mm²Range, sub-panel
10 AWG5.26 mm²Dryer, 30 A
12 AWG3.31 mm²20 A circuits
14 AWG2.08 mm²15 A lighting
16 AWG1.31 mm²Extension leads
18 AWG0.823 mm²Lamp cord
22 AWG0.326 mm²Electronics

Worked examples

  • 10 AWG is 5.26 mm², the usual size for a 30 A dryer circuit.
  • 18 AWG is 0.823 mm², typical lamp cord.
  • 6 AWG is 13.30 mm², a service-entrance conductor.

Matching metric cable

Metric cable is sold in 1.5, 2.5, 4 and 6 mm², which do not line up with AWG. 12 AWG at 3.31 mm² sits between 2.5 and 4 mm², so neither substitute is a like-for-like replacement. Match the cross-section upward and re-check the ampacity for the installation method.

Common mistakes

  • Reading AWG as a diameter in millimetres. It is a gauge number; 12 AWG is 2.05 mm across, not 12 mm.
  • Replacing 2.5 mm² with 14 AWG, which is 2.08 mm² and slightly smaller.
  • Ignoring that ampacity also depends on insulation, bundling and ambient temperature.

A last check on the numbers: 37 AWG 12 works out to 122.5 Square millimetre, and reversing that with the same factor brings you back to 37 AWG 12. Because AWG 12 to Square millimetre is a single multiplication, any tool that gives a different figure for the same input is rounding somewhere in the middle rather than only at the end.

Frequently asked questions

3.31 mm².
No. Lower AWG numbers are thicker, so 12 AWG carries more current than 14 AWG.
Not directly: 14 AWG is 2.08 mm², slightly smaller. Match the cross-section and the ampacity, not the number.